RV Electrical Load Calculator

Choose the hookup you are plugged into, tick the appliances you want to run at the same time, and this page converts their watts to amps, totals them per leg and tells you whether the pedestal breaker holds, is close, or trips. On a 50 amp pedestal you can assign each load to leg 1 or leg 2, because the two legs trip independently and it is common for both air conditioners to land on one. The appliance list starts with typical wattages, one of them anchored on a published air-conditioner spec and the rest labelled approximate, and every watt figure is a box you can type over from your own labels. It is for anyone who has ever tripped a campground breaker with a microwave and would like to know why.

Tick what runs at the same time. Watts are typical nameplate figures; the air conditioner is anchored on a published spec, the rest are approximate. Type your own label values over them. If your label gives amps, watts = amps x 120.

OnApplianceWattsLegAmps

How it works, how to use it, and what it does not cover

Every appliance you tick is converted from watts to amps at 120 volts, the nominal pedestal voltage, and the amps are summed for each leg. The page then compares each leg's total with the breaker rating for the hookup you chose. A 30 amp pedestal is a single 120 volt leg protected at 30 amps, so everything in the rig shares 30 amps and 3,600 watts. A 50 amp pedestal is a four-wire 125/250 volt receptacle delivering two separate 120 volt legs of 50 amps each; the RV's panel splits its branch circuits between them, each leg has its own 50 amp breaker and its own limit of 6,000 watts, and the 12,000 watt headline is only reachable if the loads happen to be balanced. The adapter options model a 50 amp rig on a 30 amp pedestal, where both legs are fed from the same 30 amps, and an RV plugged into a household 15 or 20 amp outlet, where the limit is the house circuit.

The verdict for each leg is OK below 80 per cent of the breaker, close between 80 and 100 per cent, and trips above 100 per cent. The 80 per cent line is the usual continuous-load rule for breakers; running above it for long periods is how they weaken and start tripping early. When a leg trips, the page names the biggest load on that leg as the one to switch off first, and shows how many amps that would free.

To use it, set the hookup, tick the realistic worst case (both air conditioners, the water heater on electric, someone making coffee while the microwave runs), and look at the leg totals rather than the grand total. On a 50 amp rig, open your breaker panel: the labels tell you which circuits are on which leg, and the calculator's default leg assignments are only a plausible split. The converter is always on; it draws little when the batteries are full and several hundred watts after a night of boondocking, which is why the breaker trips in the first hour at a new site.

What it does not cover: the RV's own branch breakers, which are usually 15 or 20 amps and will trip before the pedestal if you put a kettle and a hair dryer on the same bathroom circuit; start-up surge, which matters for generators, inverters and soft-start decisions but seldom trips a pedestal breaker; low campground voltage, which raises the current every motor draws and is the subject of our surge-protector guide; the inverter, which moves 12 volt battery energy into 120 volt loads and complicates the arithmetic when it is also charging; and propane appliances, which draw a few watts for their boards and fans and are left out. Wattages other than the air conditioner are typical figures, not measurements; a plug-in power meter replaces every one of them with a real number.

Data last verified 2026-10-28. Prices, hours and rules change; confirm with the official source before you go.

Sources

Related guides

Frequently asked questions

How many watts can a 30 amp RV hookup supply?

3,600 watts, which is 30 amps times 120 volts on a single leg. Breakers are not designed to carry their full rating indefinitely, and the usual planning rule is to keep continuous load around 80 per cent, or about 24 amps and 2,900 watts. That is one roof air conditioner, the converter and a few small loads. Add a microwave or the water heater element while the air conditioner compressor is running and you are at or over 30 amps, which is why the pedestal breaker trips just as dinner is heating.

How many watts can a 50 amp RV hookup supply?

12,000 watts, but not as one pool. A 50 amp RV outlet is a 125/250 volt four-wire connection with two separate 120 volt legs of 50 amps each. The RV's panel splits its circuits between the two legs, so each leg is limited to 50 amps and 6,000 watts on its own. If both air conditioners happen to be on the same leg, that leg can trip while the other sits nearly empty. The calculator lets you assign each appliance to leg 1 or leg 2 so you can see this; your panel's breaker labels tell you the real assignment.

What happens when a 50 amp RV is plugged into a 30 amp pedestal with a dogbone?

The adapter feeds both of the RV's legs from the one 30 amp leg, so the whole rig shares 30 amps and 3,600 watts, and the pedestal's 30 amp breaker is now the limit for everything combined. Camco rates its 30-to-50 dogbone at 125 volts and 3,750 watts. Choose that option in the calculator and it sums both legs against 30 amps. In practice this means one air conditioner at a time, and the water heater on propane.

Where do the appliance wattages come from?

The 13,500 BTU air conditioner figure is anchored on a published spec: Coleman-Mach lists its Mach 3 Plus at 13.1 amps at 115 volts, which is about 1,500 watts running. Everything else is a typical nameplate figure for that kind of appliance, labelled approximate, because models vary widely: a microwave rated 1,000 watts of cooking power draws about 1,500 watts from the wall, electric water heater elements are commonly 1,440 watts, and a converter can draw from under 100 watts to 700 or more depending on how flat the batteries are. Read the label on your own appliance and type its watts over the default; if the label gives amps, multiply by 120.

Why does the calculator ignore start-up surge?

Because pedestal breakers are thermal-magnetic and tolerate a brief surge far above their rating; what trips them is sustained current. An air conditioner compressor can draw two to three times its running amps for a fraction of a second at start, which matters a great deal for generators and inverters and for the air conditioner's own branch breaker, but it is rarely what trips a 30 or 50 amp pedestal. The sustained total is what this page checks. If your breaker trips the instant the air conditioner starts, a soft-start kit or a tired breaker is the usual answer, not a wattage total.